APPLICATION & ENGINEERING DATA STANDBY 20kW
GENERATOR SPECIFICATIONS
TYPE ................................................................................................................SynchronousROTOR INSULATION .................................................................................................Class
FSTATOR INSULATION ...............................................................................................Class
FTOTAL HARMONIC DISTORTION ..................................................................................<5%TELEPHONE INTERFERENCE FACTOR (TIF) ..................................................................
<50ALTERNATOR OUTPUT LEADS 3 PHASE ....................................................................4
wireBEARINGS...........................................................................................................Sealed
BallCOUPLING .......................................................................................................Flexible
DiscLOAD CAPACITY (STANDBY RATING) .......................................................................
20 kWEXCITATION SYSTEM .................................................................................................Direct
NOTE: Generator rating and performance in accordance with ISO85285, BS5514, SAE
J1349, ISO3046, and DIN6271 standards.
VOLTAGE REGULATOR
TYPE .....................................................................................................................Electronic
SENSING..........................................................................................................Single
Phase REGULATION ...............................................................................................................±
1% FEATURES.....................................................................................................
V/F Adjustable Adjustable Voltage and Gain LED Indicators
GENERATOR FEATURES
Revolving field heavy duty generator Directly connected to the engine Operating temperature rise 120 °C above a 40 °C ambient Insulation is Class F rated at 130 °C rise All models are fully prototyped tested
CONTROL PANEL FEATURES
SEVEN LED INDICATOR LIGHTS ADDITIONAL FUNCTIONS
System ready • Utility sensing
Low fuel pressure • Delay on utility failure for engine start
Low battery • Engine warm-up before transfer
Low oil pressure • Delay to retransfer to utility
High coolant temp/low coolant temp • Engine cooldown timer
Overspeed • Exerciser not set
INTERNAL FUNCTIONS:
3 position switch (auto, off and manual)
2 wire start for any transfer switch
Communicates with the Generac RTS transfer switch
Selectable engine speed at exercise
Governor controller is built into the master control board
Temperature range -40 °C to 70 °C
ENGINE SPECIFICATIONS
MAKE ......................................................................................................................
GeneracMODEL .......................................................................................................................In
lineCYLINDERS .......................................................................................................................
4DISPLACEMENT .....................................................................................................
1.5 LiterBORE.............................................................................................................................
2.97STROKE ........................................................................................................................
3.23COMPRESSION RATIO ................................................................................................
9.4:1INTAKE AIR SYSTEM ..............................................................................Naturally
AspiratedVALVE SEATS .....................................................................................................ReplaceableLIFTER TYPE .........................................................................................................
Hydraulic
GOVERNOR SPECIFICATIONS
TYPE .....................................................................................................................Electronic
FREQUENCY REGULATION ...............................................................................Isochronous
STEADY STATE REGULATION ....................................................................................±
0.25 ADJUSTMENTS
Speed..........................................................................................................Yes
Droop..........................................................................................................Yes
ENGINE LUBRICATION SYSTEM
OIL PUMP .....................................................................................................................
GearOIL FILTER ..................................................................................Full
flow spin-on cartridgeCRANKCASE CAPACITY .........................................................................................4
Quarts
ENGINE COOLING SYSTEM
TYPE .........................................................................................................................
ClosedWATER PUMP ......................................................................................................Belt
drivenFAN SPEED ..................................................................................................................
2550FAN DIAMETER .....................................................................................................15
inchesFAN MODE ................................................................................................................
Pusher
FUEL SYSTEM
FUEL TYPE ................................................................................Natural
gas, propane vaporCARBURETOR .....................................................................................................Down
DraftSECONDARY FUEL REGULATOR ...........................................................................
StandardFUEL SHUT OFF SOLENOID ..................................................................................
StandardOPERATING FUEL PRESSURE .........................................................................5”
- 14” H2O
ELECTRICAL SYSTEM
BATTERY CHARGE ALTERNATOR .....................................................................12V
30 AmpSTATIC BATTERY CHARGER ......................................................................................2
AmpRECOMMENDED BATTERY ...................................................................
Group 26, 525CCASYSTEM VOLTAGE..................................................................................................
12 Volts
Rating definitions - Standby: Applicable for supplying emergency power for the
duration of the utility power outage. No overload capability is available for
this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All
ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).
STANDBY 20kW
OPERATING DATA
|
|
COMMERCIAL 20 kW | |
|
KW RATING | |
20 | |
|
ENGINE SIZE | |
1.5 Liter 4 cyl. inline | |
|
GENERATOR OUTPUT VOLTAGE/KW - 60Hz 120/208V, 3-phase, 0.8 pf |
KW 20 |
AMP 69 |
CB Size 80 |
|
GENERATOR LOCKED ROTOR KVA AVAILABLE @ VOLTAGE DIP OF 35% 208 3-phase | |
34 | |
|
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of
rated load |
Natural Gas (ft3/hr.) 60 124 188 250 315 |
(gal/hr.) 0.65 1.35 2.05 2.73 3.44 |
Propane cu ft/hr24 49 75 99 125 |
|
ENGINE COOLING Air flow (inlet air including alternator and combustion air) ft3/min. System coolant capacity US gal. Heat rejection to coolant BTU/hr. Max.
operating air temp. on radiator °C (°F) Max. ambient temperature °C (°F) | |
1,528 2.0 107,000 60 (150) 50 (140) | |
|
COMBUSTION AIR REQUIREMENTS Flow at rated power 60 Hz cfm | |
91 | |
|
SOUND EMISSIONS IN DBA Exercising at 7 meters Full load at 7 meters | |
62 75 | |
|
EXHAUST Exhaust flow at rated output 60 Hz cfmExhaust temp. at muffler outlet
°F | |
177 910 | |
|
ENGINE PARAMETERS Rated synchronous RPM 60 Hz HP at rated KW 60 Hz | |
3600 34.8 | |
|
POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature Deration 3% for every 10
°C above - °C 1.65% for every 10 °F above - °F Altitude Deration 1% for every
100 m above - m 3% for every 1000 ft. above - ft. | |
25 77183 600 | |
RATING: All three phases units are rated at 0.8 power factor. All single phase
units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to
installations served by a reliable utility source. The standby rating is applicable
to varying loads for the duration of a power outage. There is no overload capability
for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications
are subject to change without notice. KW rating is based on LPG Fuel and may derate
with natural gas. Maximum wattage and current are subject to and limited by such
factors as fuelBtu content, ambient temperature, altitude, engine power and condition,
etc.
INTERCONNECTIONS STANDBY 20kWCOMMERCIAL SERIES
INSTALLATION LAYOUT UNIT WEIGHT: Steel 1020 lbs., Aluminum 930 lbs.